Customization: | Available |
---|---|
Energy Efficiency Grade: | One |
Heat Temperature: | 80-90°C |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The advantages of CO2 as a refrigerant
INVERTER CO2(R744) water/water heat pump specification | ||||||
Model | LYDS | 40ZW | 75ZW | 120ZW | 160ZW | |
Hot Water Side | Heating Capacity | kW | 39.3 | 76.3 | 118 | 156 |
Hot water capacity | L/H | 750 | 1450 | 2256 | 2980 | |
Heating power input | kW | 8.1 | 16.5 | 25 | 37.1 | |
COP | W/W | 4.8 | 4.6 | 4.7 | 4.2 | |
Cool Water Side | Cooling Capacity | kW | 31 | 59.8 | 86.2 | 118.9 |
Cool water capacity | L/H | 6000 | 10000 | 14500 | 20400 | |
COP | W/W | 3.82 | 3.63 | 3.45 | 3.2 | |
Power supply | V/Ph/Hz | 380~440V/3PH/50~60Hz | ||||
Heating type | Direct | |||||
Output water temperature | ºC | 45~90 | ||||
Input water temperature | ºC | 5~50 | ||||
Water source temperature | ºC | 10~30 | ||||
Compressor | Type | Dorin(Italy) | ||||
Circulation water pump | Brand | Wilo | ||||
Power | kW | 0.37 | 0.55 | 1.1 | 1.5 | |
Hot water connection size | mm | DN20 | DN20 | DN25 | DN40 | |
Cool water connection size | mm | DN32 | DN40 | DN50 | DN80 | |
water heat exchanger | Type | Tube-tube exchanger | SU316 | |||
Refrigerant | Type | R744/CO2 | ||||
Controller | Brand | Carel | ||||
Dimensions | Length | mm | 1500 | 1740 | 2470 | 900 |
Width | mm | 900 | 995 | 1340 | 900 | |
Height | mm | 1290 | 1540 | 1500 | 1910 | |
Unit noise level | dB(A) | 49 | 50 | 54 | 65 | |
Net weight | kg | 450 | 890 | 1050 | 900 | |
Inverter | AC | |||||
Note: | ||||||
1.Standard temperature condition: | ||||||
Water temperature: inlet 15ºC,outlet 55ºC | ||||||
Water source temperature:inlet 12ºC,outlet 7ºC |