Fuel: | Electric Heating |
---|---|
Installation: | Packaged Boiler |
Structure: | Water Tube |
Media: | Steam and Water |
Water Circulation: | Natural Circulation |
Drum Placement: | Vertical Boiler |
Customization: |
---|
Suppliers with verified business licenses
INVERTER CO2(R744) heat pump steam generator specification | |||
Model | LYDGS-150XW | ||
Standard temperature condition | Heating Capacity | kW | 151 |
Steam Volume | Ton/H | 0.21 | |
Heating power input | kW | 50.3 | |
Cooling Capacity | kW | 100.7 | |
COP | W/W | 3 | |
Power supply | V/Ph/Hz | 380~440V/50~60Hz | |
Heat Source Water Flow | M3/H | 19 | |
Rated Steam Temperature | ºC | 120 | |
Max Steam Temperature | ºC | 165 | |
Water Source Range | ºC | 40-75 | |
Steam Pressure | Mpa | 0.0-0.1 | |
Water connection pipe size | mm | DN32/DN50 | |
Refrigerant | Type | R744/CO2 | |
Dimensions | Length | mm | 2200 |
Width | mm | 1200 | |
Height | mm | 1800 | |
Unit noise level | dB(A) | 65 | |
Net weight | kg | 1600 | |
Note: | |||
1.Water Source side: Inlet water temperature 60ºC,Outlet temperature 55ºC | |||
2.Steam Side: Outlet steam temperature 120ºC |